COMMUNICATION MANUAL
GXE600 SERIES
TDKLambda
<Page>
26/79
#
3
Re gist e r Nam e
Output Current
Data Type
Register Function
Starting Address
Qty
Non-volatile
Input
Monitor value of output current
1
No
1) Register Details
This register is measurement value of output current.
Register value is normalized[Q10] signed data with rating.
Data Type
Measurement Range
Accuracy
Normalization [Q10]
-0.01 ~ 1.3 [Q10]
+ / - 1.0% of the rating (Ta=25℃)
(Integer notation)
-102 ~ 1331
-
※ The value out of measurement range is also returned, but measurement accuracy is not guaranteed.
The actual current value is calculated by the following formula.
Output current [A] = Maximum Current × Register value ( Decimal ) × 2
-10
Example : When the register reading value is "1000d" in GXE 600-48
Output current = 12.5 × 1000 × 2
-10
= 12.207 [A]
2) Register Read
R eques t PD U
Read Inputs.
Field
Byte
Value
Function code
1
0x 04
Starting Address
2
2 (0x0002)
Quantity of Registers
2
1 (0x0001)
R es pons e PD U
Read Inputs.
Field
Byte
Value
Function code
1
0x 04
Byte count
1
2 (2 x 1)
Registers value
2
Reading data.
E rror PD U
Read Inputs.
Field
Byte
Value
Function code
1
0x 84
Exception code
1
0x02
2
(0x0002)