Re gist e r Nam e
PF mode
Data Type
Register Function
Starting Address
Qty
Non-volatile
Holding
PF mode setting
1
Yes
1) Register Details
This is the configuration register for detection target when outputting a PF (Power Fail) signal.
Specify output voltage or output current as detection target by register setting value.
Use this register to select the operation mode suitable for the user's system.
The PF detection threshold is set by the PF threshold setting register.
Configuration data is retained even when input is cut off.
The meanings of register setting values are shown below.
Mode
Function
CV_PF
Outputs the PF signal when the output voltage drops below the PF threshold
CC_PF
Outputs the PF signal when the output current drops below the PF threshold
・Register setting value
CC_PF
CV_PF
Factory setting
16 bit integer
1
0
0 (CV)
* If an unspecified value is written, only the lowest bit is accepted as a valid value.
[ CV_PF ]
[ CC_PF ]
-
0
1
Data Type
Unit
112
(0x0070)
Bit