Using via Digital Data Communication
------------------------------------------------------------------------------------
83
OUTPut:HOT
: Sets Output status while POWER is ON
Function: Sets Output status while POWER is ON
Same settings as FUNCTION Settings Item 51
Format:OUTPut:HOT <NRf>
Type:SET command, QUERY command
Paramters: 0…OFF
1…MODE1(HOT START)
HOT START is valid also when recovered from ALM or TRIP
2…MODE2(HOT START)
Powers up with OUTPUT status OFF when recovered from ALM or TRIP
HOT START is valid again on next startup.
Response: Same as parameters
Restrictions: Alarm response is returned for normal SET commands in the following conditions
・While operating as a series operation slave unit
・While operating as a parallel operation slave unit
・
Sequence operation in progress
<Ex.>
OUTP:HOT 1
OUTP:HOT?
1
OUTPut:MODE
:Sets Startup Mode
Function: Sets the Output Startup Mode
Same settings as FUNCTION Settings Item 2
Format:OUTPut:MODE <NRf>
Type:SET command, QUERY command
Paramters: 0…CV Priority, High Speed
1…CC Priority, High Speed
2…CV Priority, Slew Rate can be set
3…CC Priority, Slew Rate can be set
Response: Same as parameters
Restrictions: Alarm response is returned for normal SET commands in the following conditions
・While operating as a series operation slave unit
・While operating as a parallel operation slave unit
・
Sequence operation in progress
<Ex.>
OUTP:MODE 3
OUTP:MODE?
3
Содержание ZX-S-LN Series
Страница 1: ...Constant Voltage Constant Current DC Power Supply series Instruction Manual...
Страница 13: ...About this Product 10 This is blank page...
Страница 63: ...Useful Function 60 This is blank page...
Страница 151: ...Controlling with External Analog Contact Signals 148 This is blank page...
Страница 157: ...Special Loads 154 This is blank page...
Страница 199: ...Specifications 196 This is blank page...
Страница 200: ...197 External Diagrams ZX S 400LN 400LAN 4 M3...
Страница 201: ...Appendix 198 ZX S 800LN 800LAN...
Страница 202: ...Appendix 199 ZX S 1600LN 1600LAN...