Controlling with External Analog & Contact Signals
------------------------------------------------------------------------------------
145
Analog Output Monitor (ZX-S Series Type-LAN)
This can produce the DC voltage, which is proportional with the output voltage or output current.
Use when wishing to surveillance the output with an external meter or recorder.
Outputs a “0~10V” DC for output voltage/currents of “0 to rated output”.
Please use an input impedance of a 10kΩ or more for the external meter.
Output Voltage Monitor
The accuracy for the output voltage monitor is 0.2%±2mV
Connecting
Connect the meter or recorder to accessory connector terminals No. 4 and 15.
Output Current Monitor
The accuracy for the output current monitor is 0.5%±2mV
Connecting
Connect the meter or recorder to accessory connector terminals No. 3 and 4.
IN
OUT
4
15
+
-
V
IN
OUT
4
3
+
-
V
Output current wave forms cannot be observed by the current monitor.
Control Common (No. 4 pin) is internally connected to the minus side of the output terminal.
Caution
Control Common (No. 4 pin) is internally connected to the minus side of the output terminal.
Caution
Содержание ZX-S-LN Series
Страница 1: ...Constant Voltage Constant Current DC Power Supply series Instruction Manual...
Страница 13: ...About this Product 10 This is blank page...
Страница 63: ...Useful Function 60 This is blank page...
Страница 151: ...Controlling with External Analog Contact Signals 148 This is blank page...
Страница 157: ...Special Loads 154 This is blank page...
Страница 199: ...Specifications 196 This is blank page...
Страница 200: ...197 External Diagrams ZX S 400LN 400LAN 4 M3...
Страница 201: ...Appendix 198 ZX S 800LN 800LAN...
Страница 202: ...Appendix 199 ZX S 1600LN 1600LAN...