Controlling with External Analog & Contact Signals
------------------------------------------------------------------------------------
133
Toggling Output ON/OFF with External Contacts (ZX-S Series Type-LAN)
The ZX-S Series Type-LAN can toggle the output ON/OFF using external control connectors.
The output for ZX-S Series power supplies can be toggled ON/OFF using outputs from small
capcity contact points or photocouplers.
Use a photocoupler or a small signal relay or switch with a minimum contact capcity of 5V,
2.5mA.
FUNCTION settings must be changed to “Valid” for Output ON/OFF Control at External
Contact Points to be used.
Factory default settings are set to “Invailid”.
Connecting
Wire the cables to the external control connector (accessory) terminal’s No. 1 and 2.
The external control connectors can be simply removed by pushing down the lock levers on both sides.
14
ツイストペア線
接点
フォトカプラ
または
接点開:出力OFF
接点閉:出力ON
外部接点による、出力のON/OFF
IN
OUT
1
2
Setting Procedures
See page 130 for setting procedures.
● Not suited for power contacts such as main contact points for electromagnetic contactors or
power relays etc.
● For the output ON/OFF toggle contact point, please use an insulated contact point or open
collector at the photocoupler.
Caution
Photocoupler or Contact
Twisted-Pair Wire
Open: Output OFF
Closed: Output ON
Toggling Output ON/OFF at External Contact Point
Содержание ZX-S-LN Series
Страница 1: ...Constant Voltage Constant Current DC Power Supply series Instruction Manual...
Страница 13: ...About this Product 10 This is blank page...
Страница 63: ...Useful Function 60 This is blank page...
Страница 151: ...Controlling with External Analog Contact Signals 148 This is blank page...
Страница 157: ...Special Loads 154 This is blank page...
Страница 199: ...Specifications 196 This is blank page...
Страница 200: ...197 External Diagrams ZX S 400LN 400LAN 4 M3...
Страница 201: ...Appendix 198 ZX S 800LN 800LAN...
Страница 202: ...Appendix 199 ZX S 1600LN 1600LAN...