Functional Parameter Table
V260 Series High Performance Closed-Loop Vector Inverter User Manual
70
Function
Code
Name
Setting Range and Description
Minimum
Unit
Factory
Default
Change
Limit
F8.0.07 PG zero pulse (Z pulse)
0: Void
1: Effective
1 0 ×
F8.0.08 Decoder
type
0: ABZ incremental decoder
1: ABZUVW incremental type
2: SINCOS type
3: Rotary transformer
1 0 ×
F8.0.09
PG revolution check
cycle
1~5ms 1
2ms
F8.0.10
Missing detection and
action of speed detection
signal
_ _ _ X: Speed signal detection
0: Not detect
1: Detect and treat
_ _ X _: Speed signal detection action
0: Fault alarm and free stop
1: Continue running after switching to
SVC control mode and then display the
alarm information (reserved)
2: DC bind-type brake (reserved)
1 0001
×
F8.0.11
Judging time for speed
detection signal missing
0.01~5 .00Sec.
0.01
2.00
F8.0.12
Wire breakage zero
speed signal level (as
compared to the
maximum set speed)
0~20.0 (%)
0.1
0.0
F8.0.13
Speed measuring loop
wire breakage detection
flexibility (as compared to
the maximum set speed)
0.1~100.0 0.1
5.0
F8.0.14
Detection revolution
filtering time coefficient
0(Closed), 1~50ms
1
2ms
F8.0.15
The minimum revolution
corresponding to the
feedback signal (not PG)
0~30000rpm 1
0
F8.0.16
The maximum revolution
corresponding to the
feedback signal (not PG)
0~30000rpm 1
1500
F8.0.17
Feedback revolution ratio
(motor shaft speed:
measured shaft speed)
0.010~50.000 0.001
1.000
×
6.2.35 REVOLUTION CLOSED-LOOP PARAMETER
Function
Code
Name
Setting Range and Description
Minimum
Unit
Factory
Default
Change
Limit
F8.1.18 Controller
PID
selection
0: Single PID parameter (the second
group of parameters are effective
separately )
1: Dual PID parameter (hysteresis
switching)
2: Dual PID parameter (continuous
switching)
1 2