114 Description Of Specific Functions
V260 Series High Performance Closed-Loop Vector Inverter User Manual
7.4 CONTROL COMMAND SOURCE (GROUP F0.3)
F0.3.33 Control command 1
Setting range: 0~2
Factory default: 0
F0.3.34 Control command
2
Setting range: 0~2
Factory default: 0
To select the input physical channel of the inverter control commands (start, stop, forward, reverse, jog and
reset, etc).
0: Operating panel
The running control command is given via the operating panel. Please see Chapter 5 for the use of the
operating panel.
1: External control terminal
The running control command is given via external control commands, and the terminal function is set by the
parameter
F3.0.
2: MODBUS fieldbus/standard expansion card configuration
The running control command is given via
MODBUS
fieldbus.
F0.3.35 External control quick
setup (H)
Setting range: 0000~0013
Factory default: 0000
_ _ _ X : Control command action mode
Preconditions for below instructions: the multifunctional terminal
DI3
is for
FWD
command function ([
F3.0.02
]
=
7
),
DI4
is for
REV
function ([
F3.0.03
] =
8
), and
DI5
is for three-line running control function ([
F3.0.04
] =
19
).
0: Two wire mode 1
DI4 DI3
Running
command
OFF OFF
Stop
OFF
ON
FWD
ON
OFF
REV
ON ON
Stop
1: Two wire mode 2
DI4 DI3
Running
command
OFF OFF
Stop
OFF
ON
FWD
ON
OFF
Stop
ON ON
REV
FWD
REV
DI3
DI4
COM
In
verter
Figure 7-13-A Two wire running mode 1
FWD
REV
DI3
DI4
COM
Inverter
Figure 7-13-B Two wire running mode 2