204 Warning, Alarm Diagnosis And Counter Measures
V260 Series High Performance Closed-Loop Vector Inverter User Manual
8.4 INQUIRY FOR FAILURE RECORD
This series of frequency inverter records the failure code for the recent 8 times and the output parameters of
frequency inverter for the last failure. Looking up such information can help find the reasons of failure.
The failure information and status monitoring parameters are stored uniformly. Please look up the information
referring to operating methods of keyboard.
Monitoring
items
Content
Monitoring
items
Content
Monitoring
items
Content
dE.0.00
The last failure
dE.0.09
The output current in the
last failure
dE.0.18
The accumulative
running time (h) in the
last failure.
dE.0.01
Historical failure 1
dE.0.10
The output voltage in the
last failure.
dE.0.19
The interval time (h) of
running between the
recent two failures.
dE.0.02
Historical failure 2
dE.0.11
Detected motor speed
(with speed sensor) in
the last failure.
dE.0.20
The sync output
frequency in the last
failure.
dE.0.03
Historical failure 3
dE.0.12
DC side voltage in the
last failure.
dE.0.21
dE.0.04
Historical failure 4
dE.0.13
The output torque in the
last failure.
dE.0.22
dE.0.05
Historical failure 5
dE.0.14
The target frequency in
the last failure.
dE.0.23
dE.0.06
Historical failure 6
dE.0.15
The highest temperature
of the equipment in the
last failure.
dE.0.24
dE.0.07
Historical failure 7
dE.0.16
Command status in the
last failure (see the
following table for detail).
dE.0.25
dE.0.08
The operation
frequency in the last
failure(rotor sync)
dE.0.17
The operating conditions
of frequency inverter in
the last failure (see the
following table for detail).
Description of command and operation status:
dE.0.16
LED _ _ _ X : 0: Stop command 1: Operation command
LED _ _ X _ , _ X _ _ , X _ _ _ : Retained
dE.0.17
LED _ _ _ X : Operation mode
0: V/F mode
1: Open loop vector speed
2. Closed loop vector speed
3: Open loop torque control
4: Closed loop torque control 5: V/F separation control
LED _ _ X _ : Operation status
0: Shut down 1: Start and accelerate
2: Stop and decelerate
3: Reduce frequency and decelerate
4: Stable operation
LED _ X _ _ : Electric/braking status
0: Electric operation
1: Power generation operation
LED X _ _ _ : Limit suppression
0: No action
1: Over current suppression action
2: Over voltage suppressor action
3: Under voltage suppressor action