116 Description Of Specific Functions
V260 Series High Performance Closed-Loop Vector Inverter User Manual
The inverter can run without running permission signal.
1: Permitted when the multifunctional terminal is effective (Function No. 43)
The inverter will not start until the multifunctional input terminal (Group
F3.0
) which is defined to be running
permissible (Function No.43) is effective; If it is void, the inverter will stop in the way defined by the kilometer
of this parameter, and will then automatically run again after signal recovery.
2: Command word from standard fieldbus (effective when standard expansion card is equipped)
The start permission signal is from the bus command word.
X _ _ _ : The action mode when the running permission signal is void
0: Free stop
The inverter stops outputting, and the motor stops freely.
1: Deceleration stop
The inverter will stop at deceleration mode according to preset deceleration time.
F0.4.38 Start/Stop Mode(H)
Setting range: 0000~0101
Factory default: 0000
_ _ _ X : Start mode
0: Normal start
There are no special requirements for most load start mode. normal start mode will be adopted.
1: Revolution tracking start
It is applicable to the occasion of fault resetting and restart and restart after power-off. The inverter will
automatically judge the running speed and direction of the motor, and starts the rotating motor in a smooth
and impact-free way according to the detection and judge results; See below figure for the revolution tracking
start sketch.
Not clear
command
Re-giving
command
Auto
clear
command
Deceleration stop
Free stop
Motor status
Running command
Running permission
Start permission
Deceleration time
Acceleration time
Figure 7-15 Schematic diagram of start process