Warning, Alarm Diagnosis And Counter Measures 195
V260 Series High Performance Closed-Loop Vector Inverter User Manual
Fault
code
Fault description
Possible causes
Solutions
Fu.026
Fu.027
Fu.028
The output current
of U phase is
deficient/smaller
The output current
of V phase is
deficient/smaller
The output current
of W phase is
deficient/smaller
1. The lead from frequency inverter to motor
is disconnected.
2. The driving or control panel of the
frequency inverter is faulty.
3. The three-phase winding of the motor is
faulty.
1. Eliminate peripheral failures.
2. Seek for manufacturer’s support.
3. Eliminate the failure of motor.
Fu.032
The three-phase
input voltage is
unbalanced
(can be shielded)
The imbalance rate of three-phase voltage is
larger.
1. Add AC or DC reactor.
2. Increase the capacity of frequency
inverter.
Fu.036
Fu.037
Fu.038
AI1 input is
disconnected
A12 input is
disconnected
A13 input is
disconnected
1. The wiring of input analog signal is
disconnected or analog input signal
source is inexistent.
2. Parameters related to disconnection
detection are configured improperly.
1. Inspect the wiring of analog input
signal and the analog input signal
source.
2. Modify the configuration
parameters.
Fu.039
Fin input is
disconnected
1. The wiring of pulse input signal is
disconnected or analog input signal
source is inexistent.
2. Parameters related to disconnection
detection are configured improperly.
1. Inspect the wiring of pulse input
signal and analog input signal
source.
2. Modify the configuration
parameters.
Fu.040
The rotating speed
detection loop is
disconnected
1. The speed measuring module is
incorrectly connected.
2. The wiring of speed measuring module is
disconnected.
3. The output of speed measuring module is
abnormal.
4. Relevant function codes are set
improperly.
1. Inspect the connection of speed
measuring module.
2. Modify the parameter setting.
3. Seek for manufacturer’s support.
Fu.041
The motor fails to
be connected when
the motor
parameters are
identified.
The motor fails to be connected when the
motor parameters are identified.
Connect motor.
Fu.042
U phase output is
disconnected or the
parameters are
seriously
unbalanced
1. The lead from frequency inverter to motor
is disconnected.
2. The driving or control panel of the
frequency inverter is faulty.
3. The three-phase winding of the motor is
faulty.
1. Eliminate peripheral failures.
2. Seek for manufacturer’s support.
3. Eliminate the failure of motor.
Fu.043
V phase output is
disconnected or the
parameters are
seriously
unbalanced
1. The lead from frequency inverter to motor
is disconnected.
2. The driving or control panel of the
frequency inverter is faulty.
3. The three-phase winding of the motor is
faulty.
1. Eliminate peripheral failures.
2. Seek for manufacturer’s support.
3. Eliminate the failure of motor.