Installation Of Frequency Inverter
V260 Series High Performance Closed-Loop Vector Inverter User Manual
11
3. INSTALLATION OF FREQUENCY INVERTER
3.1 INSTALLATION OF FREQUENCY INVERTER
This series of frequency inverters are wall-mounted or cabinet frequency inverters, which should be installed
vertically. In order to be in favor of circulation and heat dissipation, please install the frequency inverter at
indoor place with good ventilation. Please refer to 1.3.3 for installation environment. If there is special
installation requirement from customer, please contact with manufacturer in advance.
3.1.1 MOUNTING SURFACE
Sometimes, the temperature of cooling fin may rise to around 90
℃
, so please install the mounting surface at
the place which can stand for this temperature rise.
3.1.2 INSTALLATION SPACE
Requirements for installation spacing distance of single frequency inverter are as shown in Figure 3-1-A and
Figure 3-1-B. Reserve enough space around the frequency inverter.
120mm above
50mm above
50mm above
120mm
above
Fan
exhaust
Fan
exhaust
150mm
above
350mm above
150mm above
350mm above
3.1.3 MULTIPLE INSTALLATIONS
If install more than 2 sets of frequency inverters in device or control cabinet, please conduct parallel
installation in principle as shown in Figure 3-3. If there is no choice but vertical installation, please consider
setting partition plate as shown in Figure 3-2, to make no influence on upper frequency inverter from lower
frequency inverter.
Figure 3-1-B Installation spacing
distance (37KW above)
Figure 3-1-A Installation spacing
distance (30KW below)
DANGER
Please install it on flame-retardant object such as metal,
otherwise may cause fire.
!