Operation And Simple Running Of Frequency Inverter 37
V260 Series High Performance Closed-Loop Vector Inverter User Manual
Process
Operations
References
Set operation
control
parameters
General
parameters
Correctly set direction of rotation, acceleration
time, deceleration time, starting frequency,
starting mode, acceleration and deceleration
mode and stop mode, etc. As per the operating
conditions of driving system
Refer to F0.0.17
parameter set,
F0.1.20~F0.1.24
parameter set,
F0.4.37~F0.4.52
parameter set for starting
and stopping, and
F1.0.00~F1.0.10
parameter set for
acceleration and
deceleration
characteristics
Set operation
control
parameters
Vector control
Adjust the parameters of regulator in accordance
with load conditions, if necessary, set torque
control and limit parameters. For vector control
with PG, make sure to correctly set the
parameters of encoder.
Refer to F8.0.01 ~
F8.0.15 parameter set
for rotating speed setting
and feedback
Empty-load commissioning
inspection
Empty-load motor; start the frequency inverter
with keyboard or control terminals; inspect and
confirm the operating conditions of driving system;
Motor: stable operation, normal rotation, correct
direction, normal acceleration and deceleration
process, no abnormal vibration, noise and smell.
Frequency inverter: normal display data of
operation panel, normal operation of fan, normal
sequence of operation of relay, no vibration and
noise, etc. If there are abnormalities, please stop
and inspect immediately.
Refer to Chapter 3 and 5
Commissioning inspection
with load
Connect the load of driving system after normal
empty-load commissioning. Start the frequency
inverter with keyboard or control terminal and
gradually increase load. When the load is
increased to 50% and 100%, operate the system
for a period of time respectively to inspect whether
the operation of the system is normal or not. It
shall inspect overall during operation and observe
whether there are abnormalities, or it shall stop
and inspect immediately.
Refer to Chapter 3 and 5
Basic operation
The frequency inverter can carry out such basic
operations as general starting, running, stopping
and F/R, etc
Refer to Chapter 3 and 5
Function
operation
PLC
operation
Frequency conversion operation can be set as
single cycle execution or recycle execution. One
cycle process includes 15 execution phases
whose operating frequency, acceleration and
deceleration time, operating time and direction,
etc. And can be set separately.
Refer to F6.0.00 ~
F6.0.14 parameter set
for multi- frequency
setting function,
F6.0.15~ F6.0.45
parameter set for simple
and programmable
multi-section operation
function
Function
operation
PID operation
Users can set the preset channel and feedback
channel for PID process control as well as
parameters of PID regulator to realize the control
to industrial process.
Refer to F7.0.00 ~
F7.0.26 parameter set
for process PID function
Torque control
Torque control is used under vector control mode
and can control the output torque of the motor as
per torque command value.
Refer to F8.3.39 ~
F8.3.51 parameter set
for torque control
function
Acceleration
and
deceleration
In order to make acceleration and deceleration
process smooth and reduce mechanical impact,
users can set S curve acceleration and
deceleration function to make the speed of the
Refer to F1.0.00 ~
F1.0.10 function
parameter set