![Sunfar V260-4T0007G/4T0011P Скачать руководство пользователя страница 241](http://html1.mh-extra.com/html/sunfar/v260-4t0007g-4t0011p/v260-4t0007g-4t0011p_user-manual_1396025241.webp)
Accessories 233
V260 Series High Performance Closed-Loop Vector Inverter User Manual
Pr---- power of brake resistance
D---- braking frequency (time proportion of regeneration process accounts for the whole
process), generally it is 10%. Please refer to table below:
Type Lift
Winding
&
unwinding
Centrifuge Accidental
braking load
Proportion 20%~30% 20%~30% 50%~60%
5%
Brake resistance selection table
If need braking function of the model upon V260-4T0220, please refer to the braking unit manual.
Model
Adaptive
motor
(
KW
)
Power of
brake
resistance
(
KW
)
Brake
resistance
value
(Ω)
Brake
torque
(
100%
)
Brake unit
V260-4T0007 1.1
0.3
≥
400
100
Standard
V260-4T0011 1.1
0.3
≥
400
100
Standard
V260-4T0015 1.5
0.5
≥
300
100
Standard
V260-4T0022 2.2
0.65
≥
200
100
Standard
V260-4T0030 3.0
0.75
≥
150
100
Standard
V260-4T0040 4.0
1.0
≥
125
100
Standard
V260-4T0055 5.5
1.5
≥
85
100
Standard
V260-4T0075 7.5
2.0
≥
65
100
Standard
V260-4T0090 9.0
2.5
≥
60
100
Standard
V260-4T0110 11
2.5
≥
50
100
Standard
V260-4T0150 15
3.6
≥
35
100
Standard
V260-4T0185
18.5
4.5
≥
30
100
Standard
V260-4T0220
22
5.5
≥
25
100
Standard