Description Of Specific Functions
137
V260 Series High Performance Closed-Loop Vector Inverter User Manual
Table 7-9 Contrast table of process PID feedback switching status
Terminal status
Process PID feedback of frequency inverter
ON Process
PID
feedback
2
OFF Process
PID
feedback
1
33: Process PID sleep activation
When the sleep function is activated by multifunctional input terminals (set F7.2.34 as 2), the functional
terminal can activate process PID sleep function.
34: Torque/speed control mode switching
The functional terminal is applied to switch closed loop control mode of frequency inverter between torque
control and speed control. See the closed loop control mode of frequency inverter as following table:
Table 7-10 contrast table of closed loop control mode of frequency inverter
Terminal status
Closed loop control mode of frequency inverter
ON
Torque control mode
OFF Speed
control
mode
35: Minimum torque limiting set value selection
This function is applied to switch minimum torque limiting set value of frequency inverter (negative torque
limiting) between minimum torque limiting 1 and minimum torque limiting 2. See switching status as following
table:
Table 7-11 Minimum torque limiting selection contrast table of frequency inverter
Terminal status
Minimum torque limiting set value of frequency inverter
ON
Minimum torque limiting 2
OFF
Minimum torque limiting 1
36: Maximum torque limiting set value selection
This function is applied to switch maximum torque limiting set value of frequency inverter between maximum
torque limiting 1 and maximum torque limiting 2. See switching status as following table:
Table 7-12 Maximum torque limiting selection contrast table of frequency inverter
Terminal status
Maximum torque limiting set value of frequency inverter
ON
Maximum torque limiting 2
OFF
Maximum torque limiting 1
40: RS485 external/Standard operation panel switching
When two operation panels are inserted to frequency inverter at the same time, one is for master control
panel switching, and the other is only for monitoring, and the order cannot be inputted in.
Table 7-13 Control command channel switching and selecting table for frequency inverter
Terminal state
Control command channel of frequency inverter
ON
RS485 external panel
OFF Standard
operation
panel
42: Start permission
When parameter F0.4.37 is set as ###1or ###2, the function terminal is valid.
43: Running permission
When parameter F0.4.37 is set as #1## or #2##, the function terminal is valid.