110 Description Of Specific Functions
V260 Series High Performance Closed-Loop Vector Inverter User Manual
7.3 FREQUENCY SETUP (GROUP F0.2)
F0.2.25 Frequency setting channel 1
Setting range: 00~29
Factory default: 2
F0.2.26 Frequency setting channel 2
Setting range: 00~29
Factory default: 0
The frequency set value determined via the frequency setting source 1 is named as the set value 1; and the
frequency set value determined via the frequency setting source 2 is named as the set value 2.
0: Keypad entry 1 (keep value when stopped)
The frequency set value is determined by the value of the parameter
F0.2.29
(or
F0.3.32
). In the normal
monitoring mode, it is applicable to make direct modification with the
∧
and
∨
keys (or shuttle) on the panel.
The modified values will not be saved and will get lost after power-on.
1: Keypad entry 2 (go to zero when stopped)
Similar to the case of “0” as above, the inverter will automatically clear current set value after stop.
2: Keypad entry 3 (keep value at power off)
Similar to the case of “0,1” as above, the inverter will automatically save the current set value after power-off,
and take the saved value as the initial set value after power-on once again.
3: Setting of wheel potentiometer
Its function is equivalent to the high-precision panel potentiometer. The set resolution is the minimum
quantitative value (e.g. 0.01 Hz), and data are saved in the internal memory of the panel.
4: Remote UP/DW 1 (keep value at power off)
Multifunctional terminals are used to directly increase, decrease (Function No. 15, 16) or clear (Function No.
17) the set frequency. The terminal function is selected by parameters
F3.0.00
~
F3.0.08.
The set data will not
be saved and will get lost after power-off.
The relationship between the status setting combination of the three external switches and the current
Time
FWD jog
frequency
Frequency
Jog signal
Deceleration time
1/2/3/4
FWD jog
frequency
Jog acceleration time
[F1.0.09]
Jog deceleration time
[F1.0.10]
Frequency
Time
Jog signal
Acceleration time
1/2/3/4
Figure 7-11 FWD jog running curve