282
SIEL
Procedure
1. Open the inverter according to the inverter‘s instructions.
2. If you are fabricating the cable yourself, connect the wires as shown in the following diagram.
Solar-Log™ terminal strip connector
Inverter terminal strip
Terminal
Terminal
►
1 Data+
►
R+
►
4 Data-
►
R-
3. If no further inverter is connected, terminate the inverter according to the instructions for the inverter.
4. Close the inverter if no other inverters are to be connected.
5. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
•
Connect using a 2-wire, shielded data cable.
•
Where to connect: Terminal strip inside the inverter on the retrofitted RS485 interface card
Procedure
1. Open the inverter according to the inverter‘s instructions.
2. Connect terminals T+ and T-on inverter 1 to terminals R+ and R- on inverter 2.
Terminal strip connection inverter 1
Terminal strip inverter 2
Terminal
Terminal
►
T+
►
R+
►
T-
►
R-
3. Connect the other inverters to each other in the same way.
4. Terminate the last inverter in accordance with the inverter instructions.
5. Close the inverter.
Содержание Solar-Log
Страница 1: ...1 Components Connection Manual V 4 2 3 Solar Log EN ...
Страница 20: ...20 01 Inverter ...
Страница 366: ...366 Surpass SSE Note Feed in management Power reductions of less than 10 are set by the inverters to 10 ...
Страница 398: ...398 Appendix 113Appendix 113 1 SMA mixed wiring Fig SMA mixed wiring ...
Страница 402: ...402 02 Meter ...
Страница 444: ...444 03 Battery Systems ...
Страница 456: ...456 sonnen Note Only one battery system can be connected to a Solar Log device ...
Страница 463: ...463 04 Heating rods ...
Страница 470: ...470 05 Heating pumps ...
Страница 478: ...478 06 Sensors ...
Страница 488: ...488 07 Pyranometer ...
Страница 495: ...495 08 Smart Plug components ...
Страница 502: ...502 09 Power Charging Stations ...