52
-
No.JXC
※
-OMU0030-A
E
Any
condition
Control
power
supply is
shut down
<Condition>
Output current at the power supply circuit is abnormally high.
<Countermeasure>
Check if the actuator cable or connector is short-circuited.
Confirm the combination of the controller and the electric actuator is correct.
E
Any
condition
Control
power
supply is
shut down
<Condition>
Abnormality concerning EEPROM is confirmed.
<Countermeasure>
If the problem is not solved by supplying power again, please contact SMC.
(The write limit of the EEPROM is roughly 100,000 times)
E
Any
condition
Control
power
supply is
shut down
<Condition>
CPU is not operating properly.
(Failure of CPU and peripheral circuits, or malfunction due to noise)
<Countermeasure>
If the problem is not solved by supplying power again, please contact SMC.