11
TYPICAL APPLICATION
Fig.3 HGM8110A Typical Application Diagram
Fig.4 HGM8120A Typical Application Diagram
NOTE:
If the engine starting battery voltage is 24V, starting output, fuel output and stop output (according to user’s
configuration) should not be less than 2Ω for battery cathode resistance, if less than 2Ω, please expand relays with more
than 30A current in corresponding output. If the engine starting battery voltage is 12V, starting output, fuel output and
stop output (according to user’s configuration) should not be less than 1Ω for battery cathode resistance; if less than 1Ω,
please expand relays with more than 30A current in corresponding output.