HGM8110A/8120A Genset Controller User Manual Page 31 of 57
No.
Items
Parameters
Defaults
Description
7
Start Idle Time (0~3600)s
0
Idle running time of genset when starting.
8
Warming Up
Time
(0~3600)s
10
Warming time between genset switch on
and high speed running.
9
Cooling Time
(0~3600)s
10
Radiating time before genset stop, after it
unloads.
10
Stop Idle Time (0~3600)s
0
Idle running time when genset stop.
11
ETS Solenoid
Hold
(0~3600)s
20
Stop electromagnet’s power on time when
genset is stopping.
12
Fail to Stop
Delay
(0~3600)s
0
Time between ending of genset idle delay
and stopped when “ETS output time” is set
as 0;
Time between ending of ETS hold delay
and stopped when “ETS output time” is
not 0.
13
After Stop Time (0~3600)s
0
Time between genset stopped and
standby.
Engine Setting
1
Engine Type
Fixed value: 0
0
Default: Conventional unit (non-ECU).
2
Flywheel Teeth (10~300)
118
Tooth number of the engine, for judging of
starter
separation
conditions
and
inspecting of engine speed. See the
installation instructions.
3
Rated Speed
(0~6000)r/min
1500
Offer standard for over/under/loading
speed.
4
Speed on Load (0~100)%
90%
Setting value is percentage of rated
speed. Controller detects when it is ready
to load. It won’t switch on when speed is
under loading speed.
5
Loss of Speed
Signal Delay
(0~3600)s
5
Time from detecting speed is 0 to confirm
the action.
6
Loss of Speed
Signal Action
(0~1)
0
0: Warn; 1: Shutdown
7
Over
Speed
Shutdown
(0~200)%
114
Setting value is percentage of rated speed
and delay value also can be set.
8
Under
Speed
Shutdown
(0~200)%
80
9
Over
Speed
Warn
(0~200)%
110
Setting value is percentage of rated
speed. Delay value and return value also
can be set.
10
Under
Speed
Warn
(0~200)%
86