HGM8110A/8120A Genset Controller User Manual Page 25 of 57
No.
Type
Description
value, it will send stop signal.
16
OP Sensor Open
When controller detects sensor is open circuit, and the action
selects “Shutdown”, it will send stop signal.
17
Low OP Shutdown
When controller detects oil pressure is lower than the set value,
it will send stop signal.
18
Level Sensor Open
When controller detects sensor is open circuit, and the action
selects “Shutdown”, it will send stop signal.
19
Flexible Sensor 1 Open
When controller detects sensor is open circuit, and the action
selects “Shutdown”, it will send stop signal.
20
Flexible Sensor 1 High
When controller detects the sensor value is higher than the
max. set value, it will send stop signal.
21
Flexible Sensor 1 Low
When controller detects the sensor value is lower than the min.
set value, it will send stop signal.
22
Flexible Sensor 2 Open
When controller detects sensor is open circuit, and the action
selects “Shutdown”, it will send stop signal.
23
Flexible Sensor 2 High
When controller detects the sensor value is higher than the
max. set value, it will send stop signal.
24
Flexible Sensor 2 Low
When controller detects the sensor value is lower than the min.
set value, it will send stop signal.
25
Digital Input Port
When digital input port is set as shutdown, and the action is
active, it will send stop signal.