HGM8110A/8120A Genset Controller User Manual Page 39 of 57
No.
Type
Description
27
Reserved
28
Reserved
29
Close Generator
Control generator to take load.
30
Open Breaker
Control breaker to off load.
31
Close Mains
Control mains to take load.
32
Reserved
33
Crank Relay
34
Fuel Relay
Action when genset is starting and disconnect when
stop is completed.
35
Idle Control
Used for machine which has idles. Close before starting
and open in warming up delay; Close during stopping
idle mode and open when stop is completed.
36
Raise Speed
Action in warming up delay.
37
Drop Speed
Action between the period from “stop idle” to “failed to
stop”.
38
ETS Control
Used for engines with ETS electromagnet. Close when
stop idle is over and open when pre-set “ETS delay” is
over.
39
Pulse Drop Speed
Active 0.1s when controller enter into stop idle, used for
control part of ECU dropping to idle speed (temporary
reserved).
40
Reserved
41
Reserved
42
Pulse Raise Speed
Active 0.1s when controller enter into warming up delay;
used for control part of ECU raising to normal speed
(temporary reserved).
43
Crank Success
Close when detects a successful start signal.
44
Generator OK
Action when generator is normal.
45
Generator Available
Action in period of generator ok to high-speed cooling.
46
Mains OK
Action when mains normal.
47
Reserved
48
Common Alarm
Action when genset common warning, common
shutdown, common trips alarm.
49
Common Trip and Stop
Action when common trip and stop alarm.
50
Common Shutdown
Action when common shutdown alarm.
51
Common Trip Alarm
Action when common trip alarm.
52
Common Warn Alarm
Action when common warning alarm.
53
Reserved
54
Battery High Volts
Action when battery’s over voltage warning alarm.
55
Battery Low Volts
Action when battery’s low voltage warning alarm.
56
Charge Alt Fail
Action when charge failure warning alarm.
57