HGM8110A/8120A Genset Controller User Manual Page 50 of 57
NOTE:
Maximum set value must over minimum set value in case that the condition of too high as well as too low will
happen.
NOTE:
When setting the warning alarm, please set the correct return value; otherwise, maybe there is abnormal alarm.
When setting the maximum value, the return value must less than set value; When setting the minimum value, the return
value must over set value.
NOTE:
Please set the generator frequency value as low as possible when cranking, in order to make the starter be
separated quickly as soon as crank disconnect.
NOTE:
Configurable input could not be set as same items; otherwise, there are abnormal functions. However, the
configurable output can be set as same items.
NOTE:
HGM8110A controller has no items about mains. Pressing and holding
for a long time can exit
parameter setting menu directly and set the controller into standby mode.