HGM8110A/8120A Genset Controller User Manual Page 34 of 57
No.
Items
Parameters
Defaults
Description
generator switch on; or from generator
switch off to mains switch on.
2
Close Time
(0~20.0)s
5.0
Pulse width of mains/generator switch on.
When it is 0, means output constantly.
3
Open Time
(0~20.0)s
3.0
Pulse width of mains/generator switch
off.
4
Check Time
(0~20.0)s
5.0
Time of detecting switch auxiliary
contacts after transferred.
5
Transfer Failure
Warn Enable
(0~1)
0
0: Disable 1: Enable
6
Check Enable
(0~1)
0
0: Disable 1: Enable
7
Enable
Trip
Immediate
Mains Dropout
(0~1)
1
0: Disable 1: Enable
Module Setting
1
Power
on
Mode
(0~2)
0
0: Stop mode 1: Manual mode
2: Auto mode
2
Module
Address
(1~254)
1
Controller’s address during remote
sensing.
3
Stop Bits
(0~1)
0
0: 2 stop bits; 1: 1 stop bit
4
Language
(0~2)
0
0: Simplified Chinese 1: English 2:
Others
5
Password
(0~65535)
00318
For entering advanced parameters setting.
Scheduling and Maintenance Setting
1
Scheduled Run
(0~1)
0
0: Disable; 1: Enable
2
Scheduled Not
Run
(0~1)
0
0: Disable; 1: Enable
3
Maintenance
(0~1)
0
0: Disable; 1: Enable
Analog Sensors Setting
Temperature Sensor
1
Curve Type
(0~15)
7
SGX. See table 15.
2
Open Circuit
Action
(0~2)
0
0: Warn; 1: Shutdown; 2: No action
3
High
Temp.
Shutdown
(0~300)ºC
98
Shutdown when sensor temperature
higher than this value. Detecting only after
safety delay is over. The delay value also
can be set.
4
High
Temp.
Warn
(0~300) ºC
95
Warn when sensor temperature higher
than this value. Detecting only after
safety delay is over. The delay value and
return value also can be set.