HGM8110A/8120A Genset Controller User Manual Page 38 of 57
7.2
ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS 1-6
7.2.1
DEFINED CONTENTS OF PROGRAMMABLE OUTPUT PORTS 1-6
Table 13 Defined Contents of Programmable Output Ports 1-6
No.
Type
Description
0
Not Used
1
Custom Period 1
Details of function description please see the following.
2
Custom Period 2
3
Custom Period 3
4
Custom Period 4
5
Custom Period 5
6
Custom Period 6
7
Custom Combined 1
8
Custom Combined 2
9
Custom Combined 3
10
Custom Combined 4
11
Custom Combined 5
12
Custom Combined 6
13
Reserved
14
Reserved
15
Reserved
16
Reserved
17
Air Flap
Action when over speed shutdown and emergence
stop. It also can close the air inflow to stop the engine
as soon as possible.
18
Audible Alarm
Action when warning, shutdown, trips. Can be
connected annunciator externally. When “Alarm Mute”
configurable input port is active, it can remove the
alarm.
19
Louver Control
Action in genset starting and disconnect when genset
stopped completely.
20
Fuel Pump Control
It is controlled by fuel pump of level sensor’s limited
threshold.
21
Heater Control
It is controlled by heating of temperature sensor’s
limited threshold.
22
Cooler Control
It is controlled by cooler of temperature sensor’s s
limited threshold.
23
Oil Pre-supply
Actions in period of cranking to safety run.
24
Excite Generator
Output in start period. If there is no generator frequency
during high-speed running, output for 2 seconds again.
25
Pre-Lubricate
Actions in period of pre-heating to safety run.
26
Remote Comm. Control
This port is controlled by communication (PC).