HGM8110A/8120A Genset Controller User Manual Page 45 of 57
No.
Type
Description
mode.
key and simulate auto key input does not
work.
19
Reserved
20
Reserved
21
Inhibit Alarm Stop
All shutdown alarms are prohibited except emergence
stop. (Means battle mode or override mode)
22
Aux Instrument Mode
All outputs are prohibited in this mode.
23
Reserved
24
Reset Maintenance
Controller will set maintenance time and date as default
when input is active.
25
Reserved
26
Aux. High Temp
Connected sensor digital input.
27
Aux. Low Oil Pressure
Connected sensor digital input.
28
Remote Start (On Load)
In
Auto
mode, when input active, genset can start
automatically and take load after normal running; when
input inactive, genset will stop automatically.
29
Remote Start (Off Load)
In
Auto
mode, when input is active, genset can start
automatically and NOT take load after normal running;
when input is inactive, genset will stop automatically.
30
Aux. Manual Start
In
Manual
mode, when input active, genset will start
automatically; when input inactive, genset will stop
automatically.
31
Reserved
32
Reserved
33
Simulate Stop key
An external button can be connected and pressed as
simulate panel.
34
Simulate Manual key
35
Simulate Manual Test key
36
Simulate Auto key
37
Simulate Start key
38
Reserved
39
Reserved
40
Reserved
41
Reserved
42
Reserved
43
Reserved
44
Reserved
45
Aux Mains OK
In
Auto
mode, mains normal when input is active
(HGM8120A).
46
Aux Mains Fail
In
Auto
mode, mains abnormal when input is active