HGM8110A/8120A Genset Controller User Manual Page 42 of 57
No.
Type
Description
237
Reserved
238
Reserved
239
Reserved
7.2.2
CUSTOM PERIOD OUTPUT
Defined period output is composed by 2 parts, period output S1 and condition output S2.
While S1 and S2 are
TRUE
synchronously, OUTPUT;
While S1 or S2 is
FALSE
, NOT OUTPUT.
Period output S1, can set generator’s one or more period output freely, can set the delayed time and
output time after enter into period.
Condition output S2, can set as any conditions in output ports.
NOTE:
when delay time and output time both are 0 in period output S1, it is
TRUE
in this period.
Example,
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: output port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);
Output port 1 active, after enter “starts time” and delay 2s, this defined period output is outputting, after
3s, stop outputting;
Output port 1 inactive, defined output period is not outputting.
7.2.3
CUSTOM COMBINED OUTPUT
Defined combination output is composed by 3 parts, OR condition output S1, OR condition output S2,
AND condition output S3.
S1 or S2 is
TRUE
, while S3 is
TRUE
, defined combination output is outputting;
S1 and S2 are
FALSE
, or S3 is
FALSE
, defined combination output is not outputting.
NOTE:
S1, S2, S3 can be set as any contents except for “defined combination output” in the output setting.
NOTE:
3 parts of defined combination output (S1, S2, S3) couldn’t include or recursively include themselves.