HGM8110A/8120A Genset Controller User Manual Page 26 of 57
5.3
TRIP AND STOP ALARM
When controller detects trip and stop alarm signal, it will break generator close signal quickly and stop
the genset after high speed cooling.
Table 9 Trip and Stop Alarm
No.
Type
Description
1
Over Current
When controller detects the value is higher than the set value,
and the action selects “Trip and Stop”, it will send trip and stop
signal.
2
Maintenance Due
When count down time is 0 and the action selects “Trip and
Stop”, it will send a trip and stop signal.
3
Reverse Power
When controller detects reverse power value (power is
negative) is higher than the set value, and the action selects
“Trip and Stop”, it will send a trip and stop signal.
4
Over Power
When controller detects the power value (power is positive) is
higher than the set value, and the action selects “Trip and Stop”,
it will send a trip and stop signal.
5
Digital Input Ports
When digital input port is set as “Trip and Stop”, and the action
is active, it will send a trip and stop signal.
5.4
TRIP ALARM
When controller detects trip alarm, it will break generator close signal quickly, but not stop genset.
Table 10 Trip Alarm
No.
Type
Description
1
Over Current
When controller detects the value is higher than the set value,
and the action selects “Trip”, it will send trip signal.
2
Reverse Power
When controller detects reverse power value (power is
negative) is higher than the set value, and the action selects
“Trip”, it will send a trip signal.
3
Over Power
When controller detects the power value (power is positive) is
higher than the set value, and the action selects “Trip”, it will
send a trip signal.
4
Digital Input Ports
When digital input port is set as “Trip”, and the action is active, it
will send a trip signal.