HGM8110A/8120A Genset Controller User Manual Page 51 of 57
9
SENSORS SETTING
1.
When reselect sensors, the sensor curve will be transferred into the standard value. For example, if
temperature sensor is SGX (120°C resistor type), its sensor curve is SGX (120°C resistor type); if
select the SGD (120°C resistor type), the temperature sensor curve is SGD curve.
2.
When there is difference between standard sensor curves and using sensor, user can adjust it in
“curve type”.
3.
When input the sensor curve, X value (resistor) must be input from small to large, otherwise,
mistake occurs.
4.
If select sensor type as “None”, sensor curve is not working.
5.
If corresponding sensor has alarm switch only, user must set this sensor as “None”, otherwise,
maybe there is shutdown or warning.
6.
The headmost or backmost values in the vertical coordinates can be set as same as below,
Fig.2 Sensor Curve
Table 17 Normal Pressure Unit Conversion Form
N/m
2
(pa)
kgf/cm
2
bar
psi
1Pa
1
1.02x10
-
5
1x10
-
5
1.45x10
-
4
1kgf/cm
2
9.8x10
4
1
0.98
14.2
1bar
1x10
5
1.02
1
14.5
1psi
6.89x10
3
7.03x10
-
2
6.89x10
-
2
1