HGM8110A/8120A Genset Controller User Manual Page 30 of 57
7
SCOPES AND DEFINITIONS OF CONFIGURABLE PARAMETERS
HGM8110A/8120A
genset controllers can set the following parameters, (HGM8110A has no mains
items)
7.1
CONTENTS AND SCOPES OF PARAMETERS
Table 12 Parameter Setting Contents and Scopes
No.
Items
Parameters
Defaults
Description
Mains Setting
1
AC System
(0~3)
0
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
2
Rated Voltage (30~30000)V
230
Standard for checking mains over/under
voltage. (It is primary voltage when using
voltage transformer.)
3
Rated
Frequency
(10.0~75.0) Hz
50.0
Standard for checking mains over/under
frequency.
4
Normal Time
(0~3600)s
10
The delay from mains abnormal to normal.
5
Abnormal Time (0~3600)s
5
The delay from mains normal to abnormal.
6
Volt. Trans.(PT) (0~1)
0
0: Disable ;
1: Enable
7
Over Voltage
(0~1000)%
120
Setting value is mains rated voltage’s
percentage, and return value and delay
value can be set.
8
Under Voltage (0~1000)%
80
9
Over Frequency (0~1000)%
Disable
Setting value is mains rated frequency’s
percentage, return value and delay value
can be set.
10
Under
Frequency
(0~1000)%
Disable
11
Loss of Phase
(0~1)
1
0: Disable; 1: Enable
12
Reverse Phase (0~1)
1
Timer Setting
1
Start Delay
(0~3600)s
1
Time from mains abnormal or remote
start signal is active to start genset.
2
Stop Delay
(0~3600)s
1
Time from mains normal or remote start
signal is deactivated to stop genset.
3
Preheat Delay (0~3600)s
0
Time of pre-powering heat plug before
starter is powered up.
4
Cranking Time (3~60)s
8
Time of starter power up
5
Crank
Rest
Time
(3~60)s
10
The waiting time before second power up
when engine start fail.
6
Safety On Delay (0~3600)s
10
Alarms for low oil pressure, high
temperature,
under
speed,
under
frequency/voltage, charge fail are inactive.