![Smartgen HGM8100A Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/smartgen/hgm8100a/hgm8100a_user-manual_1297525036.webp)
HGM8110A/8120A Genset Controller User Manual Page 36 of 57
No.
Items
Parameters
Defaults
Description
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Flexible Input Port 4
1
Contents
Setting
(0~50)
0
User defined. See table 14.
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3
Active Range
(0~3)
2
0: From safety on 1: From starting 2:
Always 3: Never
4
Active Actions
(0~4)
0
0: Warn; 1: Shutdown; 2:Trip and stop 3:
Trip 4: Indication
5
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm.
6
Description
User defined.
Flexible Input Port 5
1
Contents
Setting
(0~50)
0
User defined. See table 14.
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3
Active Range
(0~3)
2
0: From safety on 1: From starting 2:
Always 3: Never
4
Active Actions (0~4)
1
0: Warn; 1: Shutdown; 2:Trip and stop 3:
Trip 4: Indication
5
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm.
6
Description
User defined.
Flexible Input Port 6
1
Contents
Setting
(0~50)
0
User defined. See table 14.
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3
Active Range
(0~3)
2
0: From safety on 1: From starting 2:
Always 3: Never
4
Active Actions (0~4)
2
0: Warn; 1: Shutdown; 2: Trip and stop 3:
Trip 4: Indication
5
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm.
6
Description
User defined.
Flexible Output Ports
Flexible Output Port 1
1
Contents
Setting
(0~239)
1
User defined period output 1 (default
output is in preheating). See table 13.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Flexible Output Port 2