Hardware
Hardware Configuration
4 - 26
SKF Multilog On-Line System IMx-M
User Manual
Figure 4 - 14.
4
–
20 mA Output Voltage Selection.
The pinouts of 4-20 mA 37-Pin D-sub are listed in
Slot Connections chapter.
Important - The usage of 4-20 mA Outputs is only for monitoring purposes.
Use relay outputs for safety alert/danger triggering.
Protection Module Serial (USB) Interface
Serial (USB) interface on a protection module may be used to transfer the protection
firmware (*.a48) and/or configuration file (*.bin) created via
to a protection module slot wise.
The USB port for the protection configuration is located on the front panel of each
protection module. See
in Drawings and Connections chapter
for the physical location.
Selecting the correct Mini-USB Cable
Ensure that the correct (isolated) Mini-USB cable is selected for use. Do not use an
ordinary Mini-USB cable.
Figure 4 - 15.
Selecting the Correct Mini-USB Cable.
Establishing a Connection between Host PC and a Protection Module
Connect a Mini-USB cable between the Host PC and the protection module as shown in
the figure below: