Hardware
Installation
SKF Multilog On-Line System IMx-M
4 - 5
User Manual
Figure 4 - 3.
Illustration of Desired Diverted Airflow.
One fan tray and an air guide plate shall be mounted for each IMx-M rack:
The fan tray must be mounted directly below each IMx-M rack.
The air guide plate must be mounted directly above each IMx-M rack.
The following cooling components are recommended:
Fan tray, article number: Rittal 3352.500
Guide frame, article number: Rittal 3357.100
Air guide plate, article number: Schroff 10713-144
When using the fan tray, the maximum allowed ambient operating temperature shall be
55 °C (
131 °F)
under normal operating conditions