Protection
Modbus
2 - 194
SKF Multilog On-Line System IMx-M
User Manual
Digital Ch Values
When a digital channel is set up for speed measurement, the Modbus register
value is shown in rpm.
Register "Combined Ch Alarm Enable/Disable" Bit Definition
Table 2-41: Register "Combined ch Alarm enable/disable" bit definition (TRUE=1).
Register "Combined Ch Alarm Enable/Disable" Bit Definition
Bit representation*
Description
(0x0000)
(No bit set)
Alarm Disabled
0x0001
Alert Low
0x0002
Alert High
0x0004
Danger Low
0x0008
Danger High
0x0010
Ch A Alert Trigger Relay (n/a for Ch B)
0x0020
Ch A Danger Trigger Relay (n/a for Ch B)
0x0040
Ch B Alert Trigger Relay (n/a for Ch A)
0x0080
Ch B Danger Trigger Relay (n/a for Ch A)
*
Important:
- Bit representation is in hexadecimal digits.
- Bit representation can be a combination of more than one condition.
Example: Bit representation of 0x006A is equal to
0x0002 Alert low +
0x0008 Danger high +
0x0020 Ch A Danger trigger relay +
0x0040 Ch B Alert trigger relay
Refer to
Bit Representation of Combined Conditions