Protection
Modbus
SKF Multilog On-Line System IMx-M
2 - 183
User Manual
Exported (Read) Modbus Registers
IMx-M item
Register
number(1)
Function
Data type
Min and Max
Modbus L2
Statistics(2)
616
Number of Short
frames
Unsigned 16 bits
0 to 65 535(4)
617
Number of Long
frames
618
Number of CRC errors
619
Number sent
620
Number received
621
Number of Rx timeout
622
Number of Uart
errors
Analog Ch 1
Alert Low
657
Analog Ch 1 Alert Low
threshold
Signed 16 bits
-32 768 to
+32 767 (see also
corresponding analog
channel Alert/Danger
Scale Factor)
Analog Ch 16
Alert Low
672
Analog Ch 16 Alert
Low threshold
Analog Ch 1
Alert High
705
Analog Ch 1 Alert
High threshold
Signed 16 bits
-32 768 to
+32 767 (see also
corresponding analog
channel Alert/Danger
Scale Factor)
Analog Ch 16
Alert High
720
Analog Ch 16 Alert
High threshold
Analog Ch 1
Danger Low
753
Analog Ch 1 Danger
Low threshold
Signed 16 bits
-32 768 to
+32 767 (see also
corresponding analog
channel Alert/Danger
Scale Factor)
Analog Ch 16
Danger Low
768
Analog Ch 16 Danger
Low threshold
Analog Ch 1
Danger High
801
Analog Ch 1 Danger
High threshold
Signed 16 bits
-32 768 to
+32 767 (see also
corresponding analog
channel Alert/Danger
Scale Factor)
Analog Ch 16
Danger High
816
Analog Ch 16 Danger
High threshold