Protection
Protection Module Configuration with IMx-M Manager
SKF Multilog On-Line System IMx-M
2 - 179
User Manual
Figure 2 - 148.
Configuring Active Alarms and Alarm Parameters for a Channel.
6.
Set the Alarm Levels parameters.
Only high level alarms will be configured because it is not a problem if there is no “toxic
waste water” in the container. (It is assumed that the emptying of the container works
as it should as long as it is not reaching the full level.)
The
Alert High
alarm is configured with the level set to 70%.
Enter time
of the Alert High are set to 1 000 ms.
Hysteresis
of the Alert High is set to 2%.
Trigger relay
of the Alert High is checked to enable relays to be drawn based on
this alarm.
A
Danger High
alarm is also configured with the level set to 80%.
Enter time
of the Danger High are set to 1 000 ms.
Hysteresis
of the Danger High is set to 2%.
Trigger relay
of the Danger High is also checked to enable relays to be drawn
based on this alarm.
The configured alarm levels are shown in the
Bar Graph
to the right.
Green
–
Normal.
Yellow
–
Alert.
Red
–
Danger.