5-1
NOTICE TO INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Stan-
dard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Program Feature or Option
Permitted in UL 864? (Y/N)
Possible Settings
Settings Permitted in UL 864
NAC Function Type
Y
SSIG, RSIG, SUPV, TRBL,
UTILITY
SSIG, RSIG, SUPV, TRBL
Relay Function Type
Y
SRELAY, RRELAY, SUPV,
TRBL, UTILITY, PRIMARY,
ALTERN, DRESET,
DHOLDER
SRELAY, RRELAY, SUPV,
TRBL, PRIMARY, ALTERN,
DRESET, DHOLDER
Manually programming NAC, programmable relay, and DACT points
allows you to set the attributes of the point to the specific values
required for the job. You can create a custom label for each point,
change the way in which the NACs, programmable relays, and DACT
operate, or add a NAC or relay to an alarm group for selective signaling.
It is recommended that you use the panel’s auto programming feature
(see Chapter 3) when initially programming the panel, or when adding
devices to an existing job. Auto programming automatically programs
the NACs, Relays, and DACT with default values. You can then use the
manual programming procedures described in this chapter to adjust the
following values.
•
Hardware Type. Identifies the specific type of device.
•
Function Type. Determines the operation of the point. For a NAC or
relay, you can set whether the device turns off on silence or reset,
etc.
•
Label. Up to 20 characters can be used to create a custom label for
the point.
•
Alarm Group. Applies to NACs and Relays. Allows you to define
selective signalling groups. Each NAC or Relay point can be asso-
ciated with up to three alarm groups, allowing you to specify which
initiating devices are allowed to activate the device.
To manually add, edit, or delete a point, you must first login at Access
Level 4. Refer to Chapter 1 for information on doing this.
If an Expansion Power Supply Module is installed in the system, you
must first set the Expansion Power Supply system option to ON before
In This Chapter
Accessing Menus . . . . . . . . . . . . . . . . . . . . . . 5-2
Programming NACs . . . . . . . . . . . . . . . . . . . . 5-2
Programming AUX Relays . . . . . . . . . . . . . . . 5-4
Programming DACT. . . . . . . . . . . . . . . . . . . . 5-6
Accessing DACT Menu . . . . . . . . . . . . . . . . . 5-6
Programming DACT Options . . . . . . . . . . . . . 5-7
Programming Contact ID (CID) Points . . . . . . 5-9
Programming Event Codes . . . . . . . . . . . . . 5-10
Saving Changes. . . . . . . . . . . . . . . . . . . . . . 5-11
Chapter 5. Manually Programming NACs,
Relays, and DACT
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание TrueAlarm 4008- 9121
Страница 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 86: ...Technical Manuals Online http www tech man com firealarmresources com...