Chapter 5. Manually Programming NACs, Relays, and DACT
5-10
point, but there is no need to specify the type of event with
the CID format. This information is automatically derived
from the point’s function type.
Note:
Default CID point values are provided in the panel.
Before changing these values, please contact an authorized
representative at the supervising station. Refer to Table 3-4
for information on the default CID codes.
1.
Follow the steps in “Accessing DACT Menu,” earlier in
this chapter. Use the <NEXT> or <PREV> keys to
choose CID Points.
<ENTER>=Accept
DACT: [CID Points]
2.
Press <ENTER>. A prompt similar to the following
appears.
[Garage
IDC1]
GRP: 01
ID: 001
This prompt consists of the following fields.
•
Point Custom Label. The top line of the prompt dis-
plays the custom label assigned to the point.
•
Grp. A 2-digit number used to group associated
devices together.
•
ID (Contact ID). a 3-digit number used to identify a
specific point/device.
3.
For each point, use the right arrow key to move between
the digits of the GRP and ID fields. Use the <NEXT>
and <PREV> keys to increment or decrement the value
of a digit.
4.
To choose another point, press the right arrow key until
the cursor is on the top line (custom label) of the
prompt. Use the <NEXT> and <PREV> keys to scroll
to another point and then repeat Step 3.
5.
When all points have been configured, press the
<ENTER> key. A prompt similar to the following
appears, asking you to confirm the changes you made.
<ENTER>=Confirm
GRP: [01]
ID:001
6.
Press <ENTER>. The prompt shown in Step 1 appears.
Programming Event Codes
Follow the procedure below only if the DACT is using the
3/1 or 4/2 reporting format.
1.
Follow the steps in “Accessing DACT Menu,” earlier in
this chapter. Use the <NEXT> or <PREV> keys to
choose Event Codes.
<ENTER>=Accept
DACT: [Event Codes]
2.
Press <ENTER>. A prompt similar to the following
appears.
[FIRE ALARM]
Code: A1
3.
For each code, use the right arrow key to move between
the letter/digit of the Code field. Use the <NEXT> and
<PREV> keys to increment or decrement the value of a
letter or digit. See Table 5-5 for a list of Event types and
their corresponding codes.
4.
To choose another code to edit or verify, press the right
arrow key until the cursor is on the top line of the
prompt. Use the <NEXT> and <PREV> keys to scroll
to another code and then repeat Step 3.
5.
When all points have been configured, press the
<ENTER> key. A prompt similar to the following
appears, asking you to confirm the changes you made.
<ENTER>=Confirm
Code: A1
6.
Press <ENTER>. The prompt shown in Step 1 appears.
Table 5-5 Event Categories and Codes
Event
3/1
BFSK
4/2
SIA
Fire Alarm
1
11
A1
FA1
Supervisory
3
33
A3
SS3
Trouble
4
F4
A4
FT4
Fire Restoral
E
E1
71
FR1
Supervisory
Restoral
E
E3
73
SJ3
Trouble Restoral
E
E4
74
FJ4
Phone Line 1
Trouble
F
FB
31
LT1
Phone Line 1
Restoral
E
EB
35
LR1
Phone Line 2
Trouble
F
FC
32
LT2
Phone Line 2
Restoral
E
EC
36
LR2
AC Failure
F
FA
6A
AT0
AC Restoral
E
EA
7A
AR0
Auto Test Report
E
EE
3A
RP0
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание TrueAlarm 4008- 9121
Страница 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 86: ...Technical Manuals Online http www tech man com firealarmresources com...