Optional Modules
The following is a list of optional modules for the 4008.
Refer to the individual instructions that accompany each
module for more information. Refer to the label inside the
door of the 4008 for the placement of optional modules.
Note:
One AUX relay module or city circuit card is
allowed.
EXPANSION POWER SUPPLY (4008-9801)
When additional notification appliance circuits are required,
an expansion power supply may be added. The expansion
power supply provides two additional 2A NACs, and fil-
tered/regulated 24 VDC, 3A power. The expansion power
supply is mounted to the right of the MSB at the bottom of
the chassis. It connects to the MSB with a ribbon harness.
The NACs on the EPS may be configured as AUX 24V
power taps. One EPS per system is allowed. The EPS must
be enabled via the panel’s System Options before use.
CITY CIRCUIT CARDS (4006-9805, 4006-9806)
The city circuit card connects to the MSB with a ribbon har-
ness to provide connections to either Remote Station
(reverse polarity), or Public Service Fire Communications
Center (local energy) receiving units. The card has two cir-
cuits - circuit 1 reports alarm or alarm/trouble events
(Remote Station only) and circuit 2 can be configured to
report trouble events or supervisory events. In the event of a
CPU failure, a city card configured for a trouble output
sends a trouble to the city circuit. The card is mounted to the
right of the MSB at the top of the chassis. The 4006-9805
and 4008-9806 city cards are identical except that the 4006-
9805 provides disconnect switches for each circuit. Model
4006-9805 must be used for Canadian applications. The City
Circuit must be enabled via the panel’s System Options
before use.
AUX RELAY MODULE (4008-9802)
The auxiliary relay module includes three relays, one each
for system alarm, supervisory and trouble conditions. LEDs
indicate active relay circuits. Normally Open or Normally
Closed contact operation is selected by shunt jumper place-
ment. Contacts are rated for 2A, 30VDC, 0.35 power factor.
Either an auxiliary relay module or a City Circuit Card may
be added to the system. Addressable relay modules are avail-
able, connecting to the system through IDNet.
ANNUNCIATOR MODULES
The 4008 supports a variety of annunciator modules. A total
of four annunciators may be added to the system, one of
which can be located in the panel (door-mounted LED
annunciator).
•
Door-Mounted LED Annunciator
. The Local Zone
LED Module provides 24 LEDs for visible zone alarm
and trouble indication. This module is standard for
ULC-S527 compliant systems (Canada). There are 10
Red and 14 Yellow LEDs. This provides a red alarm and
yellow trouble LED for up to 10 groups of devices. This
module also provides 4 Yellow LEDs, one for each of 4
NACs. The LEDs are programmable, and can be used
for other functions as appropriate per application.
Figure 1-1 Zone LED Annunciator Module
•
Remote LED/Switch Module (4610-9111).
This
module provides the following:
-
10 programmable red LEDs
-
6 programmable yellow LEDs Green “power on”
LED
-
Yellow “Alarm Silenced” LED
-
Yellow “Trouble”
-
Yellow “Comm Loss” LED
Specification
Power Supply
120 VAC, 60 Hz, 4A;
240 VAC, 50 Hz, 3A
24 VDC, 3A alarm power
24 VDC, ½A auxiliary power
Battery charger for up to 25 Ah batter-
ies, recharge per UL 864 and for up to
12.7 Ah per S527 (ULC). The
4008
back box can accommodate up to 12.7
Ah batteries
Environmental
The
4008
operates normally with ambi-
ent temperatures from 32° F to 120° F
(0° C to 49° C), inclusive.
The
4008
operates normally under non-
condensing humidity conditions up to
93% relative humidity at 90° F (32° C).
Zone 8
Zone 4
Zone 9
Zone 5
Zone 1
Zone 10
Zone 6
Zone 2
Zone 7
Zone 3
NAC 3
NAC 4
NAC 1
NAC 2
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание TrueAlarm 4008- 9121
Страница 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 86: ...Technical Manuals Online http www tech man com firealarmresources com...