Chapter 6. Manually Programming Annunciators
6-8
1.
Press the <MENU> key. Press <NEXT> or <PREV>
until the [Programming] option is displayed. Press
<ENTER>. The following displays:
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
2.
Press <ENTER>. The Programming menu appears.
[Points] is the default selection, which allows you to
make changes to a specific point’s programming.
<ENTER>=Accept
Prg:[Points]
3.
Press <ENTER>. A prompt appears, allowing you to
select the type of point to manually edit. By default,
[IDC] is the first choice.
<ENTER>=Accept
Prg:[Cards]
4.
Press <ENTER>. The display prompts you for the type
of operation you want to perform.
<ENTER>=Accept
Cards:[Add]
5.
Use the <NEXT> and <PREV> keys to scroll through
the choices until
Modify
is shown. Press <ENTER>.
The display prompts you to specify the address of the
card you want to modify.
Card=[11]
LCD
6.
Use the <NEXT> and <PREV> keys to scroll to the
address of the LCD annunciator. Press <ENTER> when
the appropriate address is shown. A prompt similar to
the following appears.
<ENTER>=ALL Events
<NEXT> = Select Events
•
Press <ENTER> to annunciate all events generated
by the panel and attached devices to the LCD. The
next prompt asks you to specify the operation of the
key-switch. See “Setting Key-Switch Operation”
below for information.
•
Press <NEXT> to select which groups of events are
forwarded to the annunciator. A series of prompts
appears, telling you to press ENTER to send a
group of events to the annunciator. See “Choosing
Event Groups to Annunciate” below.
Choosing Event Groups to Annunciate
After selecting <NEXT>, as described in Step 6 of the previ-
ous section, you are prompted to specify whether you want
to annunciate Fire events on the LCD.
<ENTER>=Accept
Send FIRE Events: [Yes]
1.
Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
appears. The next prompt asks whether you want to
annunciate Supervisory Events on the LCD.
<ENTER>=Accept
Send SUPV Events: [Yes]
2.
Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
appears. The next prompt asks whether you want to
annunciate Trouble Events on the LCD.
<ENTER>=Accept
Send TBL Events: [Yes]
3.
Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
appears. The next prompt asks whether you want to
annunciate signal silence and system reset messages on
the LCD.
<ENTER>=Accept
Send Reset/Silence: [Yes]
4.
Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
appears. See “Setting Key-Switch Operation” below for
information on the next prompt that appears.
Setting Key-Switch Operation
The key-switch operation selection allows you to select
whether or not the LCD's key-switch is required to be
inserted and activated in order for the keypad's operation to
take effect. The first prompt appears as follows.
<ENTER> = Default Key
<NEXT> = Select Key
1.
Press <ENTER> to require the use of the key for all
LCD operations (system reset, ACK, signal silence).
Press <NEXT> to see the following prompt, which asks
if you want to require the key to use the Fire Ack key.
<ENTER>=Accept
FIRE ACK: [Yes]
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание TrueAlarm 4008- 9121
Страница 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 86: ...Technical Manuals Online http www tech man com firealarmresources com...