6-1
This chapter describes
•
Programming LEDs on the
Local Zone LED annunciator
, which
is a door-mounted annunciator containing 10 Red and 14 Yellow
LEDs, providing a red alarm and yellow trouble LED for each of 10
initiating device circuits. This module also provides 4 Yellow
LEDs, one for each of 4 NACs. The LEDs are programmable, and
can be used for other functions as appropriate per application.
•
Programming LEDs on the
Remote LED/Switch Annunciator
.
-
10 programmable red LEDs
-
6 programmable yellow LEDs (no default operation)
-
Green “power on” LED (not programmable)
-
Yellow “Alarm Silenced” LED (not programmable)
-
Yellow “Trouble” (not programmable)
-
Yellow “Comm Loss” LED (not programmable)
-
Tone-Alert (not programmable).
-
Switches for ACK, Alarm Silence, System Reset, and Lamp
Test.
Note:
These switches are not programmable.
-
Key switch to enable switch functions.
For Canadian applications, one red LED and one yellow LED must
be programmed for each Alarm Group and each NAC. Yellow
LEDs must be programmed for indicating Earth Detect, City/
DACT disconnect, and Signal Silence Inhibit enabled. If the total
number of Alarm Groups plus NACs exceeds 10, an additional
remote annunciator shall be mounted adjacent to the panel.
•
Programming the three
panel LEDs
. Typical applications for these
LEDs include waterflow indicator and Earth fault indicator.
•
Programming the
LCD Annunciator
. Programming consists of
identifying which groups of events are sent to the LCD annunciator,
and determining whether the keyswitch must be turned on before
using the system reset, alarm silence, and acknowledge keys.
For Canadian applications, the LCD annunciator is only suit-
able for supplementary applications.
Note:
The <Exit/Clear> key is used to back out of menus or displays
and return to the top-level menu structure. Where possible, the <Exit/
Clear> key backs out one level at a time. There are cases, however, that
the Exit/Clear key will return the operator directly to the top-level
menu.
In This Chapter
Adding an Annunciator. . . . . . . . . . . . . . . . . . .6-2
Accessing Annunciator Menus. . . . . . . . . . . . .6-2
Programming LEDs Located on Zone Annunciator
and Remote LED/Switch Modules . . . . . . . . . .6-3
Programming Panel and LCD LEDs . . . . . . . .6-6
Programming LCD Annunciator Attributes . . . .6-7
Saving Changes to the Job . . . . . . . . . . . . . . .6-9
Chapter 6. Manually Programming
Annunciators
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание TrueAlarm 4008- 9121
Страница 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 86: ...Technical Manuals Online http www tech man com firealarmresources com...