Chapter 5. Manually Programming NACs, Relays, and DACT
5-9
3.
Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
4.
Press <ENTER>. The prompt shown above Step 1 reap-
pears.
5.
Press the <NEXT> key. The prompt for the Reporting
Format appears.
Reporting Format
Before you select the Communications Format Code, deter-
mine, from an authorized person at the supervising station,
the required reporting format.
<ENTER> = Accept
Opt: [Report Format]
1.
Press <ENTER>. The following prompt appears.
Report Format
[Contact ID]
The DACT can report in any of the following communi-
cation formats.
•
3/1 pulse
=
Three-digit account code followed by
one-digit reporting code, double round at 20 pulses
per second (PPS). Allows programmable reporting
codes. Refer to “Programming Event Codes” later
in this chapter.
•
4/2 pulse
=
Four-digit account code followed by
two-digit reporting code, double round at 20 PPS.
Allows programmable reporting codes. Refer to
“Programming Event Codes” later in this chapter.
•
BFSK
=
Three-digit account code followed by
two-digit reporting code, single transmission of
constant tones. Features built-in error checking and
fixed reporting codes.
•
SIA
=
Level 1 compatibility. Four-digit account
code features tonal acknowledge, basic reports, and
fixed reporting codes.
•
Contact ID (Default).
Uses a four digit account
code, followed by a two- digit group number and
three digit contact number.
2.
Use the NEXT and PREV keys to move from one
choice to another.
3.
Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
4.
Press <ENTER>. The prompt shown above Step 1 reap-
pears.
5.
Press the <NEXT> key. The prompt for the AC Fail
Delay appears.
AC Fail Delay
The AC Fail Delay allows you to specify the interval
between power loss at the panel and when the DACT noti-
fies the supervising station of the power loss. AC fail delay
is selectable from 0-24 hours.
AC Fail Delay
[06] Hrs
1.
Use the NEXT and PREV keys to move from one
choice to another ( 0-24 hours).
2.
Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
3.
Press <ENTER>. The prompt shown above Step 1 reap-
pears.
4.
Press the <NEXT> key. The prompt for the Test Report
Time appears.
Test Report Time
This option specifies the time at which the Test Report Event
is sent to the supervising station. Time is set in 24 hour, mil-
itary, format.
<ENTER> = Accept
Opt: [Test Rpt Time]
1.
Press <ENTER>.
Test Rpt Time
[02] : 00
2.
Use the NEXT and PREV keys to increment or decre-
ment the hour setting (two digits on left). Use the right
arrow key to move the cursor to the minutes (two digits
on right). Use the NEXT and PREV keys to increment
or decrement the minutes setting.
3.
Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
4.
Press <ENTER>. The prompt shown above Step 1 reap-
pears.
5.
Press the <EXIT/CLEAR> key. The prompt for setting
DACT options reappears. Press the <NEXT> key to
access either the CID Points or Event Codes menus.
Programming Contact ID (CID)
Points
Follow the procedure below only if the DACT is using the
Contact ID (CID) reporting format. CID reporting format
requires you to specify the group and Contact ID for each
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание TrueAlarm 4008- 9121
Страница 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 86: ...Technical Manuals Online http www tech man com firealarmresources com...