Chapter 3. Auto-Programming
3-2
3.
Press <NEXT> or <PREVIOUS> until [CONFIGURE
ALL] is displayed, then select it by pressing <ENTER>.
A warning message appears, indicating that the current
configuration will be deleted.
4.
The display indicates the progress of the Auto Program
operation. When the process is complete, the total num-
ber of IDNet devices found during Auto Program dis-
plays.
AutoProgram Complete
Total Devices: 200
5.
When <EXIT/CLEAR> is pressed, you are prompted to
save the new configuration or continue editing. Refer to
“Saving the Configuration” later in this chapter.
Detect New Hardware
This option adds newly found devices and cards to the exist-
ing configuration. It will also change any devices in the con-
figuration that have changed (e.g. photo device changed to a
sounder base photo).
1.
Press <MENU> to select the main menu and press
<NEXT> or <PREVIOUS> until the [Auto-Program]
menu item is displayed. Press <ENTER>.
FIRE ALARM
SUSPENDED
2.
Press <NEXT> or <PREVIOUS> until [DETECT
NEW] is displayed, then select it by pressing
<ENTER>. A warning message appears, indicating that
the current configuration will be changed.
3.
The display will indicate the progress of the Auto Pro-
gram operation. When the process is complete, the total
number of IDNet devices found during the Auto Pro-
gram is displayed:
AutoProgram Complete
Total Devices: 200
4.
When <EXIT/CLEAR> is pressed, you are prompted to
save the new configuration or continue editing.
Restore Factory Defaults
This option restores the 4008 to its original, factory default
configuration. All custom programming and devices are
erased from the configuration.
1.
Press <MENU> to select the main menu and press
<NEXT> or <PREVIOUS> until the [Auto-Program]
menu item is displayed and then press <ENTER>.
FIRE ALARM
SUSPENDED
2.
Press <NEXT> or <PREVIOUS> until [RESTORE
FACTORY DEFAULT] is displayed, then select it by
pressing <ENTER>. A warning message appears, indi-
cating that the current configuration will be deleted.
3.
The LCD indicates that the factory default configuration
is being recreated, and then the panel automatically
restarts.
RESTORING DEFAULT
Edit System Options
System Options allow you to set the panel’s automatic func-
tions.
1.
Press <MENU> to select the main menu and press
<NEXT> or <PREVIOUS> until the [Auto-Program]
menu item is displayed and then press <ENTER>.
FIRE ALARM
SUSPENDED
2.
Press <NEXT> or <PREVIOUS> until [SYS
OPTIONS] is displayed, then select it by pressing
<ENTER>. The first prompt appears similar to the fol-
lowing:
<ENTER>=Accept
Opt:[Time/Date]
3.
For each option, press <ENTER> and then use the
<NEXT> and <PREV> keys to review the options.
Press <ENTER> when the option is set to the appropri-
ate value. Refer to Table 3-1 for information on each
option.
Note:
Detailed descriptions for all system options are
located in Chapter 7 of this manual.
Table 3-1 System Options
Option
Settings
Time/Date Format
Choose 12- or 24-hour format
Active Status
Reminder
Choose:
•
ON or OFF (default = OFF).
•
Set reminder interval (1-12 hours;
default = 8)
•
Set Signal duration (0-60 sec-
onds; 0=on until ack; default=5)
Alarm Silence/Reset
Inhibit
Choose a timer range from 0-60 min-
utes (default=0 - no inhibit)
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание TrueAlarm 4008- 9121
Страница 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 86: ...Technical Manuals Online http www tech man com firealarmresources com...