Chapter 6. Manually Programming Annunciators
6-3
<ENTER>=Accept
Prg:[IDC
4.
Use The <NEXT> and <PREV> keys to scroll to the
appropriate choice and then press <ENTER>.
•
LED. Use this selection for programming the fol-
lowing:
-
LEDs on 4610-9111 Remote LED/Switch
Annunciator.
-
LEDs on Local Zone LED Annunciator (door-
mounted annunciator).
•
INPUT. Option not applicable to this panel.
•
USER SWITCH/LED (Panel LEDs). Use this
option to program the panel’s three LEDs and the
LCD Annunciator.
Programming LEDs Located on
Zone Annunciator and Remote LED/
Switch Modules
Use the procedures outlined in this section to program any of
the following:
•
LEDs on Local Zone Annunciator
•
LEDs on Remote LED/Switch Module
Note:
The three LEDs on the front of the display are pro-
grammed in a different manner. Refer to ”Programming
Panel LEDs” at the end of this chapter for information.
Mapping LEDs to Software Points
Figure 6-1 identifies the way in which the software points
map to the LEDs on the annunciators. For example, to con-
trol the LED in the upper left corner of the Local Zone LED
Annunciator, you need to program Point 17.
Programming Overview
Programming an LED consists of performing the following
tasks
•
Identify which point is being monitored by the LED
(called the reference point).
•
Identify which point state (fire alarm, trouble, etc.) trig-
gers the LED to turn on. This is called the mode.
See “Programming the LED’s Mode and Reference Point”
later in this chapter.
For example, you can associate an LED with a smoke detec-
tor point and have the LED turn on only when the point
enters a trouble state.
Default Programming
The LEDs on the Local Zone LED and Remote LED/Switch
annunciators have the pre-defined operations listed in Table
6-1 and Table 6-2.
In both tables, a default function of FIRE means the LED
illuminates if a current-limited condition occurs on the cor-
responding reference point. A default function of TROU-
BLE means the LED illuminates if a short occurs on the
corresponding reference point.
Figure 6-1 Mapping LEDs to Software Points
Point 7
Point 8
Point 5
Point 6
Point 22
Point 4
Point 17
Point 20
Point 15
Point 16
Point 13
Point 14
Point 11
Point 12
Point 9
Point 10
Point 23
Point 24
Point 21
Point 2
Point 19
Point 1
Point 3
Point 18
Fire Alarm Annunciator
CONTROL
ENABLE
Lamp
Test
ACK
Reset
Alarm
Silence
Alarm
Silenced
Power
Comm Lost
Trouble
Point 17
Point 20
Point 22
Point 4
Point 5
Point 6
Point 7
Point 8
Point 9
Point 10
Point 11
Point 12
Point 13
Point 14
Point 15
Point 16
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание TrueAlarm 4008- 9121
Страница 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 86: ...Technical Manuals Online http www tech man com firealarmresources com...