2-1
Back Box Mounting
The back box can be surface-mounted or semi-flush mounted to the
wall. Use separate conduit entrances for power-limited and non-power
limited wiring.
AC supply, battery supply, and City Connect wiring are all non-power
limited wiring.
Removing Electronics Assembly
Use either a #6 Torx or a slot-head screwdriver to remove the four
screws that secure the electronics assembly to the back box.
Conduit Entrances and Wire Routing
•
Nine knockouts are provided for conduit connection. Refer to Fig-
ure 2-1 for knockout locations.
•
Power limited wiring
must be located only in the shaded area of
the cabinet.
•
AC power (non-power limited) wiring must be run in separate con-
duit from all other wiring, as shown in Figure 2-1.
Non-power lim-
ited wiring must be separated from power limited wiring by a
minimum of 1/4".
Figure 2-1 Power-Limited (Shaded) and
Non-Power Limited Wiring Areas
Expansion
Power Supply
TB1
TB2
TB3
Battery
AC Voltage
Connection
Battery
Connection
Battery
DACT
City Connect
Module
In This Chapter
Back Box Mounting . . . . . . . . . . . . . . . . . . . . .2-1
General Wiring Guidelines . . . . . . . . . . . . . . . .2-2
IDNet Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Class A/Class B NAC Wiring . . . . . . . . . . . . . .2-5
Remote Annunciator Comm Wiring . . . . . . . . .2-8
Digital Alarm Communicating Transmitter (DACT)
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
Auxiliary 24V Power Wiring . . . . . . . . . . . . . . 2-11
City Connect Module Wiring. . . . . . . . . . . . . .2-12
Auxiliary Relay Wiring . . . . . . . . . . . . . . . . . .2-13
AC Supply Wiring . . . . . . . . . . . . . . . . . . . . . .2-14
Battery Wiring. . . . . . . . . . . . . . . . . . . . . . . . .2-15
Depleted Battery Cutout. . . . . . . . . . . . . . . . .2-16
Safety Ground/Ferrite Bead . . . . . . . . . . . . . .2-16
Replacing Lithium Battery . . . . . . . . . . . . . . .2-17
Periodic Testing and Maintenance . . . . . . . . .2-17
Chapter 2. Installation/System Checkout
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание TrueAlarm 4008- 9121
Страница 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 86: ...Technical Manuals Online http www tech man com firealarmresources com...