3-1
The Auto-Program option provides the ability to quickly and automati-
cally program the panel’s components and features for general alarm
operation. It automatically scans the serial communication channel, add-
ing any annunciators found, polls the IDNet channel and configures any
IDNet devices found, and adds any option cards found.
Auto-Program can perform the following:
•
Reconfigure all hardware
•
Add new hardware
•
Restore factory defaults
•
Edit system option settings
Understand the following when using Auto-Program:
•
The panel does not operate as a fire alarm system during Auto-Pro-
gramming.
•
Auto-Program performs a IDNet duplicate address search and ter-
minates if duplicate addresses are found.
•
DACT information must be manually programmed (i.e. phone
numbers, account information, etc.). Refer to Chapter 5 for infor-
mation on doing this.
Note:
Auto-Program is protected at Access Level 4. In order to
perform an Auto-Program operation, the operator must first login
at Access Level 4. Refer to Chapter 1 for information on logging
in to the system
.
Refer to “Default Programming Assignments” in this chapter for a
description the default programming assigned to each type of point.
Configure All
This option starts the panel with a new configuration. If a previous con-
figuration is present and this option is selected, it erases the previous
configuration and creates a new one with the currently connected hard-
ware.
1.
Press <MENU> to select the main menu.
2.
Press <NEXT> or <PREVIOUS> until the [Auto-Program] menu
item is displayed and then press <ENTER>. The following appears:
FIRE ALARM
SUSPENDED
In This Chapter
Configure All. . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
Detect New Hardware . . . . . . . . . . . . . . . . . . .3-2
Restore Factory Defaults . . . . . . . . . . . . . . . . .3-2
Edit System Options. . . . . . . . . . . . . . . . . . . . .3-2
Restore Default System Options . . . . . . . . . . .3-3
Saving the Configuration . . . . . . . . . . . . . . . . .3-3
Default Programming Assignments . . . . . . . . .3-3
Chapter 3. Auto-Programming
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание TrueAlarm 4008- 9121
Страница 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 86: ...Technical Manuals Online http www tech man com firealarmresources com...