Chapter 4. Manually Programming IDNet Points
4-3
.
Note 1.
The operation of sounder bases is controlled by
the Single Station system option. See Chapter 7
of this manual for additional information.
Note 2.
A multi-detector base, coupled with a combina-
tion photo/heat sensor,
uses two addresses
. Make
sure to set the address on the base to an even
number, and do not set any other device to the
address that you set plus one. The even number
represents the Photo portion of the combination
sensor. The address plus one represents the heat
portion of the sensor.
Note 3.
The HEAT, RHEAT, IHEAT, and SHEAT func-
tion types set the heat detector to a fixed sensitiv-
ity of 135°F. An alarm is initiated when the
temperature rises beyond this temperature.
The OHEAT, ROHEAT, IOHEAT, and SOHEAT
function types set the heat detector for rate-of-rise
operation. With this hardware type, if the temper-
ature rises beyond 135°F or if the temperature
rises at a rate of 15°F per minute, an alarm is ini-
tiated.
Table 4-1 Hardware Types for Sensors/Bases
Sensor
Models
Base
Models
Use this
Hardware
Type
4098-9714
4098-
9714C
Photo-
Electric
Smoke
Detector
Sensor
4098-9755
4098-9755C
Two-wire duct base w/o relay
PHOTO
4098-9792
4098-9792C
Detector base w/o remote LED
4098-9789
4098-9789C
Detector base with remote LED
4098-9756
4098-9756C
Four-wire duct base with relay
RPHOTO
4098-9791
4098-9791C
Detector base with relay
RPHOTO
4098-9793
4098-9793C
Isolator base
IPHOTO
4098-9794
4098-9794C
Sounder base
See Note1 below
SPHOTO
4098-9733
4098-
9733C
Heat
Detector
Sensor
4098-9792
4098-9792C
Detector base w/o remote LED
HEAT
OHEAT
4098-9789
4098-9789C
Detector base with remote LED
4098-9791
4098-9791C
Detector base with relay
RHEAT
ROHEAT
4098-9793
4098-9793C
Isolator base
IHEAT
IOHEAT
4098-9794
4098-9794C
Sounder base
See Note 1 below.
SHEAT
SOHEAT
4098-9754
4098-
9754C
Combina-
tion Photo
Electric
Smoke
Detector
and Heat
Detector
4098-9795
4098-9795C
Multi-detector sounder base
See Note 1 and Note 2 below.
SPHOTO &
SHEAT
4098-9796
4098-9796C
Multi-detector base with LED
See Note 2 below.
PHOTO &
HEAT
Table 4-2 Hardware Types, IDNet Modules
Module
Use this
Hardware
Type
4090-9007
Zone Individual Addressable Module (IAM) for
Class A or B Signal Circuits
SIGNAL
4090-9001
Supervised Individual Addressable Module (IAM)
IAM
4090-9002
Indiv. Addressable Module with Relay
RIAM
Table 4-1 Hardware Types for Sensors/Bases
Sensor
Models
Base
Models
Use this
Hardware
Type
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание TrueAlarm 4008- 9121
Страница 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Страница 86: ...Technical Manuals Online http www tech man com firealarmresources com...