Installation Instructions Document No. 466-1574
.
14
Option 09: DL Code (Downloader Code)
Add programs the downloader access code. The
Downloader Code is used during Control Panel pro-
gramming with the ITI ToolBox. The Control Panel’s
downloader code must match the downloader access
code in the ITI ToolBox account in order to program
the Control Panel using the ITI ToolBox.
Delete resets the code to 12345.
CAUTION!: The downloader code should always be
changed to avoid competitor theft.
Option 10: Entry Delay
Add programs the entry delay. Enter time in seconds.
The range is 005-120 seconds (3 digits must be en-
tered). Entry delay beeps will sound when the delay is
activated. The panel will sound beeps corresponding
to the arming level every 5 seconds. For example, you
will hear 2 beeps every 5 seconds if the panel is armed
to level 2. The entry delay beeps will sound every sec-
ond during the last 10 seconds of the delay to warn the
user that the delay is about to expire.
Delete sets the delay to 5 seconds.
For UL listed systems, the entry delay should not ex-
ceed 45 seconds.
Option 11: Exit Delay
Add programs the exit delay. Enter time in seconds.
The range is 005-120 seconds (3 digits must be en-
tered). The exit delay beeps will occur when the panel
is armed and when the exit delay has expired. The exit
delay beeps correspond to the arming level. For ex-
ample, you will hear 2 beeps if arming to level 2. The
panel will sound three sets of warning beeps if a sen-
sor that requires restoral is open during the exit delay
if auto arm is off (option 38). The panel will protest if
a sensor that requires restoral is open during the exit
delay if auto arm is on (option 38).
Delete sets the delay to 5 seconds.
For UL listed systems, the exit delay should not ex-
ceed 45 seconds.
Option 12: Phone Mod 1
Add sets the report content and format which the pri-
mary phone number uses. The range is 0-3.
Delete sets the phone mod to 0.
Alarms include: Fire, Intrusion, Emergency, Silent,
and Alarm Cancels.
Non-Alarms include: Latchkey, No Activity, Open-
ings, Closings, Fail to Open, Fail to Close, Force
Armed, AC Power Failure, CPU Low Battery, and
Trouble Restorals.
All includes: Alarms and Non-Alarms.
UL has only verified compatibility with the ITI
CS5000 Digital Alarm Communicator Receiver.
Option 13: Phone Mod 2
Add sets the report content and format that the second-
ary phone number uses. Range is 0-9.
Delete sets the phone mod to 0.
Option 14: DTMF Dialing
Add enables DTMF dialing.
Delete enables pulse dialing.
Table 9 Phone Mod 1
Enter #
Reports
Format
0
All
SIA
1
All
Contact ID
2
Alarms
SIA
3
Alarms
Contact ID
Table 10 Phone Mod 2
Enter #
Reports
Format
0
All
SIA
1
All
Contact ID
2
Alarms
SIA
3
Alarms
Contact ID
4
Non-Alarms
SIA
5
Non-Alarms
Contact ID
6
Phone 1 failure
SIA
7
Phone 1 failure
Contact ID
8
Latchkey, No Activity, Phone Test,
Openings, Closings, Fail to Open/
Close, AC Power Restorals/Fail-
ures
Pager
9
Same as Phone Mod 8 plus
Alarms
Pager