Option 24: AC Power Failure
Add enables AC power failure reports. The panel
LEDs will shut off and an AC power failure report
will be sent to the central station if the Control Panel
has lost power for 15 minutes. The Control Panel will
report AC power restoral when power returns to the
Control Panel.
Delete disables AC power failure and restoral reports.
Option 25: CPU Low Battery
Add enables CPU low battery reports. A low battery
report will be sent to the central station when the Con-
trol Panel’s lithium battery voltage drops below 6.2
volts or the rechargeable battery drops below 6.5
volts.
Delete disables CPU low battery reports.
Option 26: Fail to Communicate
Add enables fail to communicate. If the Control Panel
is not able to connect to the CS when it’s trying to re-
port an alarm, the Control Panel will indicate this with
trouble beeps and in the status message.
Delete disables fail to communicate.
Option 27: Ring/Hang/Ring
Add enables ring/hang/ring to use with ToolBox and
remote phone access. This feature is useful when pro-
gramming a Control Panel in a home with an answer-
ing machine.
Delete disables ring/hang/ring. The Control Panel
will not answer.
Program ring/hang/ring by number.
If ring/hang/ring is programmed as:
Program # 1 -
1. Call the Control Panel and let the phone ring
twice then hang up.
2. Wait 10-40 seconds and call the Control Panel
again.
3. The Control Panel should answer on the first
ring.
Program # 2 - Repeat steps 1 & 2 before the Control
Panel will answer.
Program # 3 - Repeat steps 1 & 2 twice before the
Control Panel will answer.
The following table identifies the phone commands to
be used when using remote phone control.
CODE = any access code except utility access codes
1 and 2
Option 28: No Delay from KeyChain Touchpad
Add arms with no entry delay when using the Key-
Chain Touchpad.
Delete arms with an entry delay when using the Key-
Chain Touchpad.
Option 29: Control Panel Alarms
Add enables the Control Panel’s piezo to sound
alarms. Alarms will sound from the Control Panel.
Table 12 Ring/Hang/Ring Program Numbers
Program # Control Panel will answer after:
1
ring/hang/ring or 10 rings
2
ring/hang/ring/hang/ring or 10 rings
3
ring/hang/ring/hang/ring/hang/ring or 10 rings
4
10 rings
Table 13 Phone Commands for Remote
Access*
Control Panel Function
Phone Command
DISARM
* + CODE + 1
ARM Doors/Windows
* + CODE + 2
ARM Doors/Windows with No
Entry Delay
* + CODE + 2 + 2
ARM Motion Sensors
* + CODE +3
ARM Motion Sensors with
Latchkey
* + CODE + 3 + 3
ARM Doors/Windows and
Motion Sensors
* + CODE + 2 + 3
ARM Doors/Windows with No
Entry Delay and Motion Sen-
sors with Latchkey
* + CODE + 2 + 2 + 3 + 3
Toggle Lights
* + CODE + 0
System Status
* + CODE + # + 1
Audio Verification
* + CODE + 5 + X (X = a
command from the audio
verification command set).
See Table 15 on page 15
* = Not Available with Basic Model