Setting options
• 3RW5 HMI High Feature
Menu: "Parameters > Soft Starter > Parameter set 1 / 2 / 3 > Motor protection > Temperature
sensor"
Access protection to the 3RW5 HMI High Feature is not active or has been reset.
• With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Parameters" > Window "Work area" > "Soft Starter > Parameter set 1 / 2 / 3 > Motor protection"
• With a fieldbus via a 3RW5 communication module:
– With SIRIUS Soft Starter ES (TIA Portal) Premium / Professional (only via a 3RW5 PROFINET
or PROFIBUS communication module)
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP)
– User program
You can find additional information on the parameters that can be set via the fieldbus in the
manual of the respective 3RW5 communication module.
Parameters
WARNING
Automatic restart following fault acknowledgment/restart.
Can cause death or serious injury.
The 3RW55 and 3RW55 Failsafe soft starters immediately continue to operate with the values
specified by the control following error acknowledgment / restart. Outputs are activated when
the ON condition is met.
Take appropriate measures to prevent unintentional restarting and to ensure a defined start of
the system.
Functions
8.3 Motor protection
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
170
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006