9.7
Execute HMI diagnostics with the 3RW5 HMI High Feature
With the diagnosis, you can display the diagnosis state of the 3RW5 HMI High Feature and check
correct functioning of the 3RW5 HMI High Feature with various tests.
Requirements
• 3RW5 HMI High Feature
Menu: "Diagnosis > HMI"
Note
Self-tests
To be able to start the self-tests with a 3RW5 HMI High Feature with firmware version V3.1, the
motor connected to the 3RW5 soft starter must be switched off.
3RW5 HMI High Feature with firmware version V3.1 or earlier: During the self-test, you cannot
switch off the motor on the 3RW5 HMI High Feature. If you are controlling the motor via the
3RW5 HMI High Feature, switch off the motor before a self-test.
Parameter
Diagnostic value
Comment
Diagnosis state
Shows all active diagnostic messages (faults, warn‐
ings, device state).
Self-test
Test LEDs
The device LEDs of the 3RW5 HMI High Feature are
tested one after the other. The display shows which
device LED is currently being controlled. Navigate
through the test operation with the OK key.
Test buttons
The 3RW5 HMI High Feature keys are tested one
after the other. The display shows which keys must
be actuated in sequence in order to perform the
test.
Test display
The 3RW5 HMI High Feature runs a color program
on the display. Navigate through the test operation
with the OK key.
9.8
Performing diagnostics of the 3RW5 communication module with
the 3RW5 HMI High Feature
With the diagnosis, you can display the diagnosis state of the 3RW5 communication module.
Requirements
• 3RW5 HMI High Feature
Menu: "Diagnosis > Communication module"
• 3RW5 communication module (accessory)
Messages and diagnostics
9.8 Performing diagnostics of the 3RW5 communication module with the 3RW5 HMI High Feature
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006
263